    ceiling support wires. An independent means of secure support shall be provided and shall be permitted to be attached to the assembly. Where independent support wires are used, they shall be distinguishable by color, tagging, or other effective means from those that are part of the fire-rated design. Exception: The ceiling support system shall be

Securing and Supporting Cables and Raceways – Jade Learning

    https://www.jadelearning.com/blog/securing-and-supporting-cables-and-raceways-2/
    Jun 21, 2016 · EMT must be secured at least every 10 ft. and within 3 ft. of every outlet box, junction box, device box, cabinet, conduit body, or other termination. An exception allows EMT to be fastened up to 5 ft. apart if structural members like joists or rafters do not permit fastening every 3 ft.

Code Guide EC&M

    https://www.ecmweb.com/cee-news-magazine-archive/article/20894958/code-guide
    Nothing in the NEC states that you cannot use the same supports for conduit as for other systems. Although Section 300.11(B) generally prohibits the use of conduit as support for anything else, it does not mention the use of water pipe or other systems (other than ceiling grids and wires) for support of conduit.

supporting EMT - Electrician Talk - Professional ...

    https://www.electriciantalk.com/f5/supporting-emt-21229/
    Feb 24, 2011 · According to the NEC. Yes, no? ... 358.1 ARTICLE 358— ELECTRICAL METALLIC TUBING: TYPE EMT be securely fastened in place and supported in accordance ... You, me, and everyone else. I do not think couplings are terminations; one support per stick is fine. Conduit bodies are LBs and LRs, etc. where I would agree you do need a strap within 3'. ...

Conduit Fittings and Supports ~ Electrical Knowhow

    https://www.electrical-knowhow.com/2013/06/conduit-fittings-and-supports.html
    Rigid metallic conduit and electrical metallic tubing both require support. Conduit should be fastened by straps to the ceiling or wall, or supported on hangers from the ceiling at least every 10 feet (Figure 11). Conduit should be fastened within 3 feet of a box (5 feet of unbroken lengths are allowed if structural members do not permit fastening within 3 feet).

Support of Steel Conduit / Tubing - Steel Conduit

    https://steeltubeinstitute.org/steel-conduit/resources/installation-guides/support-raceways/
    Steel conduit / tubing run through openings in metal or wood studs : Such openings can be used for support where the openings are no more than 10 feet apart. Secure fastening at termination points …

NEC 2017 Support and Securing Requirements Sports ...

    https://quizlet.com/164281298/nec-2017-support-and-securing-requirements-flash-cards/
    Start studying NEC 2017 Support and Securing Requirements. Learn vocabulary, terms, and more with flashcards, games, and other study tools.

Article 370 - Boxes, Conduit Bodies, and Fittings ...

    https://www.ecmag.com/section/codes-standards/article-370-boxes-conduit-bodies-and-fittings
    Besides rigid metal and intermediate metal conduit, rigid nonmetallic conduit and EMT are permitted as means of support. Using rigid nonmetallic conduit or EMT as support is only permitted if the raceway’s trade size matches, or exceeds, the conduit body’s trade size.

Supports for Rigid Metallic Conduit - Wire Size Calculator

    http://wiresizecalculator.net/tables/conduitsupportstable.htm
    These tables list the maximum distance between conduit supports for rigid metallic and non-metallic conduit. Supports for Rigid Metallic Conduit Source: NFPA 70, National Electrical Code…

EMT Strapping Code Mike Holt's Forum

    https://forums.mikeholt.com/threads/emt-strapping-code.65360/
    Jul 13, 2009 · The code states EMT must be strapped with in 3' of boxes, panels, conduit bodies... Menu. Home. Forums. ... The 2008 NEC adds a requirement for support between two boxes, if 18" or less with no concentrics, support is not needed. S. ... The purpose of supports is not necessarily to keep conduit from falling off a wall, I can do that with #9 tie ...